Batterieüberwachung - Industrielle Kennzeichnung Plotterbeschriftung Druckerbeschriftung Etiketten

Direkt zum Seiteninhalt

BMS Batterieüberwachungssystem

Anwendungen:  UPS; Energiemanagement; Telekommunikation; Kritische Batteriegestützte  Anwendungen; Aufzugssysteme

Battmaster® ist ein komplexes  Lizenzfreies Batterieüberwachungssystem, basierend auf drahtloser  Kommunikation.
Misst und speichert  jede Batterie: Batteriespannung, Temperatur; Strom, interner Wiederstand und  Entladezyklus.
Leichte und einfache  Installation und Inbetriebnahme.


System Components:

  • Central Unit (CU) -  1 per system
    • Wireless data  collector unit
    • 100-240V power  supply, backup batteries (~1.5h)
    • Supports up to 1024  DAMs and 64 IDAMs
    • Provided with 4GB  SD card (about 5 years of logging)
    • 100BASE-TX  Ethernet, full speed USB 2.0, Modbus/TCP
    • Embedded webserver  for remote monitoring
    • Manages e-mail and  SMS notifications
    • Stores user  settable alarm thresholds
  • Data Acquisition  Module (DAM)
    • 1 per battery -  Wireless voltage, temperature and internal resistance logger
  • Current Acquisition  Module (IDAM)
    • 1 per string of  batteries - Wireless current and environmental temperature logger
    • Powered by battery  or external power supply
  • BATTMASTER®  software
    • System  configuration and monitoring
    • Database of events  and measurements, data review
    • Real time system  monitoring
    • Data export to .CSV  or .PNG formats Communication

  • Wireless (license  free frequency, proprietary network protocol) between (I)DAMs and CU, range 100m  (open air)
  • USB, LAN between CU  and PC • GSM (Quad Band) - for SMS notifications
  • Dry contacts for  monitoring system alarms
  • Isolated Digital  Inputs for external custom control Monitored Battery Types
  • 2...12V lead acid  batteries (other chemistries on request) Monitored Battery Parameters
  • Voltage  (measurement accuracy: ±1.5%)
  • Temperature  (-20...80°C, ±2°C)
  • Internal resistance  (1...300mΩ, ±10% or  ±1mΩ)
  • Discharging cycles
  • Current: 300A range ±(2.4% +3A) / 600A range ±(4% +4A)
  • Battery operating  time Redundancy
  • 2 x NiMH  rechargeable batteries for CU backup (~1.5h)
  • (I)DAMs store  measures and events in case of temporary communication failure Mechanical
  • CU: size  82x150x46mm, weight 250g, ABS enclosure
  • (I)DAM: size  81x56x21mm, weight 40g, ABS enclosure, with VELCRO tape for fixing
  • Current Clamp: size  185x55x40mm, weight 180g (300A) size 203x70x37mm, weight 230g (600A)

Änderungen an der  Spezifikation sind möglich. Bitte beachten Sie das aktuelle Produktdatenblatt.


Zurück zum Seiteninhalt